Sprinkler Inspection & Testing
Quarterly, annual and five-year inspection, testing and maintenance under NFPA 25, with deficiencies ranked, photographed and quoted so you can act on them.
Overview
NFPA 25 assigns tasks to different intervals: weekly, monthly, quarterly, annual and multi-year. We map every task to your systems and put them on one recurring calendar, so nothing falls between visits.
Each visit ends with a report that separates impairments, deficiencies and recommendations, with photos and a quote for any corrective work.

Every NFPA 25 task mapped to your building.
What we do
01
Scheduled automatically on your building's calendar, with reminders before each visit.
02
Main drains, waterflow alarms, dry pipe trips and backflow forward-flow tests.
03
Internal pipe inspections for obstructions, corrosion and debris, plus check valve internals.
04
Impairments, deficiencies and recommendations separated and photographed.
05
A quote for every deficiency and crews to complete the repairs.
06
We show your team the weekly and monthly checks expected between our visits.
Standards & frequency
We build these intervals into your service calendar, so tasks happen on time and records are ready when your fire marshal or insurer asks.
| Component | Task | Typical frequency |
|---|---|---|
| Control valves | Inspect position and condition | Weekly if sealed; monthly if locked or electrically supervised |
| Waterflow alarm devices | Test | Quarterly (mechanical); semiannually (vane and pressure switch) |
| Sprinklers & visible piping | Inspect from floor level | Annually |
| Main drain | Test | Annually, more often for some supply arrangements |
| Dry pipe valve | Trip test | Annually; full-flow trip every 3 years |
| Gauges | Replace or calibrate | Every 5 years |
| Internal piping | Assessment | Every 5 years |
Summary of commonly adopted NFPA 25 editions. Your adopted edition, local amendments and AHJ determine actual requirements.
How it works
01
We document risers, valves, devices and system types on the first visit.
02
Every task is mapped to a recurring schedule with reminders.
03
Findings are photographed and ranked in a clear report.
04
Approved repairs are scheduled, completed and documented.
Questions
Have a question about your building? Call 218-262-9553 or send a request and a specialist will follow up.
NFPA 25 places responsibility for inspection, testing and maintenance on the property owner or their designated representative. Owners usually contract the work, but the obligation and the records stay with the owner.
An impairment means a system, or part of it, is out of service. A deficiency is a condition that affects or could affect performance without taking the system out of service. Impairments need immediate action and notification; deficiencies get prioritized repairs.
Yes. Many owners handle weekly and monthly visual inspections in-house. We provide checklists and training, and we handle the quarterly, annual and multi-year tasks.
Reports are posted to your customer portal after each visit and emailed to your contacts. They are also what your fire marshal and insurer will ask to see.
Our 24/7 line connects you with an on-call coordinator who can dispatch a technician, help you plan fire watch, and document the impairment for your records.
218-262-9553
Emergency service