Backflow Testing & Repair hero

Backflow Testing & Repair

Backflow Testing That Keeps Your Water Supply Protected

Annual testing of backflow prevention assemblies on fire service connections, plus repair kits, rebuilds and replacements, with results filed with your water utility.

Annual testingUtility submissionsRebuilds & replacements

Overview

Protecting the city's water and your sprinkler supply

Sprinkler systems connect to the public water supply through backflow prevention assemblies that stop system water from flowing back into drinking water. Water utilities and NFPA 25 both expect them to be tested every year.

We test double check and reduced pressure assemblies, repair failed checks and relief valves, and send results to your water utility where required.

  • Double check valve assemblies
  • Reduced pressure zone assemblies
  • Detector check assemblies
  • Annual forward-flow tests
  • Rebuild kits and check replacements
  • Results filed with your water utility
Backflow Testing & Repair overview
Same-visit rebuilds

Common kits carried on our vehicles.

What we do

Testing, repair and paperwork in one visit

Get A Quote

01

Annual Testing

Assembly tests with documented differential readings.

02

Repairs & Rebuilds

Check, seat, spring and relief valve repairs using manufacturer kits.

03

Replacements

New assemblies when parts are obsolete or bodies are damaged.

04

Forward-Flow Tests

Confirm the assembly passes system demand flow, as NFPA 25 requires.

05

Utility Paperwork

Test reports submitted on the forms your water utility requires.

06

Freeze Protection

Heat and enclosure checks for assemblies in vaults and unheated rooms.

Standards & frequency

Typical backflow requirements

We build these intervals into your service calendar, so tasks happen on time and records are ready when your fire marshal or insurer asks.

TaskRequirement sourceTypical frequency
Assembly testWater utility / plumbing codeAnnually
Forward-flow testNFPA 25Annually
Internal inspectionNFPA 25Every 5 years
Control valves on the assemblyNFPA 25Weekly or monthly, by valve type

Local water utilities may set their own testing and reporting rules. We follow the stricter requirement.

How it works

A clear process from first call to closeout

01

Locate & access

We confirm the assembly location and plan the brief shutdown.

02

Test & record

Differential readings recorded for each check and relief valve.

03

Repair if needed

Failed components rebuilt and the assembly retested.

04

File results

Passing results sent to your water utility and portal.

Questions

Backflow Testing & Repair FAQs

Have a question about your building? Call 218-262-9553 or send a request and a specialist will follow up.

Why does the water utility require backflow testing?

Backflow assemblies protect public drinking water from contamination. Utilities require annual testing to confirm each assembly works, and they track results by address.

What happens if our assembly fails?

We identify the failed component, quote the repair and in most cases rebuild the assembly on the same visit or a follow-up, then retest and file the passing result.

Will testing take our sprinkler system offline?

Testing requires closing shutoff valves briefly, which impairs the system. We notify your monitoring company, keep the impairment short and restore the system before we leave.

Do you test domestic and irrigation assemblies?

Our focus is fire service assemblies, but we can test domestic and irrigation assemblies on the same visit when it is convenient for you.

Related services

Often paired with this service

All services
Sprinkler Inspection & Testing

Sprinkler Inspection & Testing

NFPA 25 inspection, testing and maintenance programs.

Learn more
Fire Pumps & Standpipes

Fire Pumps & Standpipes

Churn tests, annual flow tests and standpipe testing.

Learn more
Fire Sprinkler Systems

Fire Sprinkler Systems

Design, installation and retrofits for new and existing buildings.

Learn more

System impairment, leak or alarm trouble?

Our 24/7 line connects you with an on-call coordinator who can dispatch a technician, help you plan fire watch, and document the impairment for your records.

218-262-9553

Emergency service